Thermal Characteristics of Staggered Double-Layer Microchannel Heat Sink.

Entropy (Basel) · 2018 · PMC7513062 · PMID 33265626

1
hedged sentence
closest p
boldest claim

The sentences

an increasing trendno p-value reported
When the vertical rib thickness is small enough, for example W r = 0.1 mm, the thermal resistance of the staggered DLMCHS shows an increasing trend with the increasing offset, which means the conventional DLMCHS with zero offset has the smallest thermal resistance and shows the best thermal performance.